ATEX sensors for hazardous areas
Intrinsically safe temperature sensors under our own certification — resistance thermometers and thermocouples, made in Hanau.
ATEX sensors measure temperature where flammable gases, vapours or dusts may occur: in chemicals and petrochemicals, painting and drying plants, mills, silos and spray booths. GHI manufactures intrinsically safe Pt100 resistance thermometers and type K, N and J thermocouples for zones 0, 1 and 2 as well as zones 20, 21 and 22. The EU type-examination certificate is issued to GHI — we mark our products ourselves, issue the declaration of conformity ourselves and do not depend on any subcontractor for the Ex version.
Our certification — and what it covers
GHI is itself an ATEX manufacturer. The EU type-examination certificate and the IECEx certificate are issued to GHI, and production is monitored by notified body 2004 (Bureau Veritas). The approval covers the WME and TME measuring inserts and the WML and TML sheathed sensors — on their own and installed in our thermowells and connection heads.
Certificates and parameters
EPS 25 ATEX 1 060 X, Rev. 1 · IECEx EPS 25.0012X, Issue 1 · Cable sensors WKF: IBExU 10 ATEX 1062 X (Ex eb/tb)
- Without thermowell: II 1G Ex ia IIC T1…T6 Ga · II 2G Ex ib IIC T1…T6 Gb · II 2D Ex ib IIIC T440 °C…T63 °C Db
- With thermowell: II 1/2G Ex ib IIC T1…T6 Ga/Gb · II 1/2D Ex ib IIIC T200 440 °C…T200 63 °C Da/Db
- Measuring range in the hazardous area −50 … +450 °C · ambient temperature at the connection head −40 … +85 °C
- Intrinsic safety parameters: Ui 30 V · Ii 70 mA · Pi 500 mW (total over all contacts) · Ci 250 pF/m · Li 50 µH/m
- Standards: EN IEC 60079-0:2018 · IEC 60079-11:2023 · EN IEC 60079-26:2024
Not covered are flameproof enclosures (Ex d) and process temperatures above +450 °C. Tell us the zone, equipment group and temperature class and we will design the version.
Which version suits your zone?
Zone and installation determine the type of protection and the marking. Choose the row that matches your measuring point.
| Application | Version | Marking | Resistance thermometer | Thermocouple |
|---|---|---|---|---|
| Zone 0 — gas continuously or for long periods | Measuring insert or sheathed sensor without thermowell, type of protection Ex ia | II 1G Ex ia IIC T1…T6 Ga | Sheathed sensors → | Sheathed thermocouples → |
| Zone 1 — gas occasionally | The same sensors in type of protection Ex ib | II 2G Ex ib IIC T1…T6 Gb | Measuring inserts → | Measuring inserts → |
| Sensor in zone 0, connection head in zone 1 | Measuring insert in thermowell, installed in the partition wall | II 1/2G Ex ib IIC T1…T6 Ga/Gb | Thermowell thermometers → | Thermowell thermocouples → |
| Zone 21 — combustible dust | Measuring insert or sheathed sensor without thermowell | II 2D Ex ib IIIC T440 °C…T63 °C Db | Sheathed sensors → | Sheathed thermocouples → |
| Zone 20/21 — dust, installed in the partition wall | Measuring insert in thermowell | II 1/2D Ex ib IIIC T200 440 °C…T200 63 °C Da/Db | Thermowell thermometers → | Thermowell thermocouples → |
| Measurement on the pipeline, permanently connected cable | WKF cable sensor in increased safety | Type of protection Ex eb / tb to IBExU 10 ATEX 1062 X | Cable sensors → | – |
ATEX versions at a glance
RESISTANCE THERMOMETER · MEASURING INSERT
WME — resistance thermometer measuring insert
Spring-loaded and replaceable for existing thermowells, with terminal block, stranded wires or head-mounted transmitter.
without thermowell: II 1G Ex ia IIC T1…T6 Ga
in thermowell: II 1/2G Ex ib IIC T1…T6 Ga/Gb
Ø 3.0 / 6.0 mm · 1× or 2× Pt100 · Ex ia and Ex ib
RESISTANCE THERMOMETER · SHEATHED SENSOR
WML — sheathed resistance thermometer
Mineral-insulated sheath, bendable, fast response. With connecting cable, free ends or connector.
II 1G Ex ia IIC T1…T6 Ga
II 2G Ex ib IIC T1…T6 Gb
II 2D Ex ib IIIC T440 °C…T63 °C Db
Ø 1.0–6.0 mm · stranded wires, LEMO, M12
THERMOCOUPLE · MEASURING INSERT
TME — thermocouple measuring insert
Sheathed measuring insert type K or N for existing thermowells, spring-loaded and replaceable.
without thermowell: II 1G Ex ia IIC T1…T6 Ga
in thermowell: II 1/2G Ex ib IIC T1…T6 Ga/Gb
Ø 3.0 / 6.0 mm · 1× or 2× element
THERMOCOUPLE · SHEATHED SENSOR
TML — sheathed thermocouple
Bendable sheathed sensor type K, N or J, measuring junction insulated or grounded.
II 1G Ex ia IIC T1…T6 Ga
II 2G Ex ib IIC T1…T6 Gb
II 2D Ex ib IIIC T440 °C…T63 °C Db
Ø 1.0–6.0 mm · stranded wires, thermocouple connector, LEMO, M12
RESISTANCE THERMOMETER · WITH THERMOWELL
Ex thermowell resistance thermometers
Eleven designs to DIN 43772 for screwing in, welding in or with flange — with certified WME measuring insert and Ex connection head.
II 1/2G Ex ib IIC T1…T6 Ga/Gb
II 1/2D Ex ib IIIC T200 440 °C…T200 63 °C Da/Db
Ø 6–14 mm · head form B, DAN/BUZ
THERMOCOUPLE · WITH THERMOWELL
Ex thermowell thermocouples
The same eleven designs as thermocouples — with certified TME measuring insert and Ex connection head.
II 1/2G Ex ib IIC T1…T6 Ga/Gb
II 1/2D Ex ib IIIC T200 440 °C…T200 63 °C Da/Db
Ø 6–14 mm · type K, N or J
INCREASED SAFETY
WKF — cable sensor in Ex eb/tb
Sensor tip with permanently attached cable, for plant and machinery in hazardous areas.
Type of protection Ex eb / tb
to IBExU 10 ATEX 1062 X
Ø 2.5–6.0 mm · silicone, PTFE, glass fibre
Understanding ATEX — the basics in brief
Zones, equipment categories and EPL
The zone describes how often an explosive atmosphere occurs and thus determines which equipment category may be installed:
- Gas: zone 0 (continuous) → category 1G, EPL Ga · zone 1 (occasional) → 2G, Gb · zone 2 (rare, short-term) → 3G, Gc
- Dust: zone 20 → 1D, Da · zone 21 → 2D, Db · zone 22 → 3D, Dc
- Equipment for zone 0 may always be used in zones 1 and 2 as well, but not the other way round
Type of protection intrinsic safety: Ex ia and Ex ib
Intrinsic safety limits the energy in the circuit so far that neither a spark nor heating can cause ignition. Ex ia is approved for zone 0, Ex ib for zone 1. The sensor alone does not make the measuring point intrinsically safe: it must be connected to a certified intrinsically safe circuit, i.e. an isolating repeater, Zener barrier or transmitter with intrinsically safe input.
Reading the marking — example II 1/2G Ex ib IIC T4 Ga/Gb
Every symbol has a meaning, and this is exactly what the operator checks:
- II — equipment group for all areas except mining
- 1/2G — partition-wall installation: the tip is in zone 0, the connection head in zone 1
- Ex ib — type of protection intrinsic safety
- IIC — highest explosion group, includes hydrogen and acetylene
- T4 — temperature class: maximum surface temperature 135 °C
- Ga/Gb — equipment protection level inside/outside the partition wall
Intrinsic safety parameters and the verification
For verifying intrinsic safety, the sensor parameters are compared with the values of the isolating repeater: Ui 30 V, Ii 70 mA and Pi 500 mW apply as the total over all contacts — with two measuring elements, therefore combined, not per circuit. In addition, the cable-length-dependent values Ci 250 pF/m and Li 50 µH/m apply. On request we prepare the intrinsic safety verification to EN IEC 60079-11, section 5.7, as a test document for your records.
Temperature class and surface temperature
The maximum surface temperature results from ambient temperature and supplied power. For the dust zones the marking is T440 °C…T63 °C, with thermowell as a T200value. The ambient temperature at the connection head may be between −40 and +85 °C, the measuring range of the sensor in the hazardous area between −50 and +450 °C.
Special conditions for safe use
The certificate carries the suffix X. Three points must be observed during installation and operation:
- For installation in a partition wall to zone 0 or 20, an additional thermowell is required
- The process connection must be leak-tight
- The metal housing must be earthed via the installation
What we do not offer
Being clear saves a query: our approval covers only the type of protection intrinsic safety “i”. We do not offer flameproof enclosures (Ex d), and the approval ends above +450 °C process temperature. As a rule we do not use third-party certificates — what is on our type plate is our own certificate.
What is supplied with the sensor
Every Ex sensor comes with a type plate with full marking, EU declaration of conformity and operating instructions. On request we add factory calibration with test report, inspection certificate and the intrinsic safety verification. Please state the required scope directly in your enquiry.
Approved and made in Hanau
GHI has been building temperature sensors since 1970 and manufactures at its Hanau site. Ex production runs under a quality assurance system monitored by Bureau Veritas, and the company is certified to ISO 9001. As a result, Ex versions add no extra lead time compared with the standard version.
No hazardous area?
We supply the same designs without Ex approval too — with the same configurator and the same lead times.
Typical industries
Chemicals & petrochemicals
Pharma & biotechnology
Food & beverages
Plastics & extrusion
Energy, power plants & hydrogen
Machinery & plant engineering
Please contact us
We are happy to help with questions about products, versions and delivery times.
Dennis Kühne
Phone: +49 6181 504 93 18
Mobile: +49 160 91437153
E-mail: info@ghi-gmbh.de
Zones, types of protection and marking explained
What Ex ia, Ex ib and Ex eb mean, which zone requires which equipment category, how to read a type plate — and which of our versions is approved where.