Skip to main content Skip to search Skip to main navigation

Temperature transmitters

Head- and rail-mounted transmitters from Siemens, Endress+Hauser, ABB and INOR — configured, programmed and tested by us in our own laboratory.

A transmitter converts the sensor signal into a 4…20 mA signal. That pays off as soon as the cable gets longer or interference is involved: a thermoelectric voltage of a few millivolts picks up everything on its way to the control cabinet, a current signal does not. If the transmitter sits directly in the connection head, the interference-proof section starts at the sensor.

We supply the transmitters fitted and set to your measuring range — or separately as a replacement. The programming and a calibration certificate come from our own laboratory.

Mounting in the connection head

The most common design: the transmitter sits in the form B head and replaces the terminal block there.

SITRANS TH320

HART · SIL 2/3 · Ex ia

SITRANS TH320

Siemens

Pt100, thermocouple, resistance, voltage · galvanically isolated

Technical data →

iTEMP TMT82

HART 7 · SIL 2 · ATEX

iTEMP TMT82

Endress+Hauser

one or two sensors · screw or push-in terminals

Technical data →

TTH300

HART · SIL · Zone 0

TTH300

ABB

Pt100 and thermocouple · broad Ex approval package

Technical data →

IPAQ-C330

HART · ATEX, IECEx, FM

IPAQ-C330

INOR

universal input: RTD and thermocouple · galvanically isolated

Technical data →

IPAQ-C520

Dual input · SIL 2

IPAQ-C520

INOR

two sensors on one transmitter · redundancy or difference

Technical data →

IPAQ-C530

HART

IPAQ-C530

INOR

Pt100 · set by us to 0…400 °C

Technical data →

APAQ-C130

4…20 mA

APAQ-C130

INOR

Pt100 and Ni100 · without galvanic isolation · the economical solution

Technical data →

iTEMP TMT31

4…20 mA

iTEMP TMT31

Endress+Hauser

Pt100 · without HART · measuring range set at the factory

Technical data →

Mounting on the DIN rail

For the control cabinet — when there is no space in the connection head or the transmitter has to stay accessible.

SITRANS TR320

HART · SIL 2/3 · Ex

SITRANS TR320

Siemens

the same transmitter as the TH320, for the DIN rail

Technical data →

IPAQ-R330

0.08 % · Bluetooth · ATEX

IPAQ-R330

INOR

universal input · 1,500 V AC isolated · operating hours counter

Technical data →

IPAQ-R530

HART

IPAQ-R530

INOR

thermocouple type K · set by us to 0…400 °C

Technical data →

Which one fits?

Your requirementMatching transmitter
Only Pt100, no HART, price decidesAPAQ-C130 or iTEMP TMT31
Thermocouple and Pt100 on one typeIPAQ-C330, TTH300 or SITRANS TH320
Safety-related measurement (SIL 2)iTEMP TMT82, SITRANS TH320 or IPAQ-C520S
Zone 0 / Zone 1TTH300, SITRANS TH320 or iTEMP TMT82 in an Ex version
Two sensors at one measuring pointIPAQ-C520S (dual input)
Mounting in the control cabinet instead of the headSITRANS TR320, IPAQ-R330 or IPAQ-R530
Configuration without unscrewing the control cabinetIPAQ-R330 (NFC and Bluetooth)

Tell us the the sensor, measuring range and output — we set the transmitter and deliver it ready to use, with a calibration certificate on request. info@ghi-gmbh.de · +49 6181 504 93 18