APAQ-C130 — INOR
Programmable head-mounted transmitter for Pt100 and Ni100 — the economical solution when 4…20 mA is enough.

Small, programmable, without HART: the APAQ-C130 takes a Pt100 or Ni100 in a 2-, 3- or 4-wire connection and outputs 4…20 mA. On sensor break or short circuit the signal goes to ≤ 3.6 mA — so the control room detects the fault immediately.
It has no galvanic isolation. Where that is needed, we use the IPAQ-C330.
Technical data
| Installation | Connection head |
| Input | Pt100 and Ni100 in a 2-, 3- or 4-wire connection |
| Output | 4…20 mA |
| Galvanic isolation | none |
| Supply voltage | 6…32 V DC |
| Sensor break / short circuit | ≤ 3,6 mA |
| Programming | to the measuring range you want, by us before delivery |
Versions in our stock
| GHI article number | Version |
|---|---|
| HMUAPAQC130RT00 | Pt100 / Ni100, programmable, 4…20 mA (INOR 70C130011) |
| 70R4600010 | APAQ-C130 RTD — digital head transmitter for Pt100 |
| 70C1300211 | APAQ-C130 TC — version for thermocouples |
Enquire about the APAQ-C130
We configure and programme the transmitter to your measuring range — tell us the sensor, range and output. info@ghi-gmbh.de or +49 6181 504 93 18
Back to the overview Temperature transmitters · We carry out programming and calibration in our own laboratory .