Thermocouples: types and tolerances to DIN EN 60584
A thermocouple generates a temperature-dependent thermoelectric voltage at the junction of two metals — the Seebeck effect. It is robust, fast and can be used up to 1,700 °C.
Which type suits which purpose, how large the permissible deviation is and which voltage is present at which temperature is set out in DIN EN 60584-1.
The types at a glance
| Type | Material pairing (+ / −) | Application range | Property |
|---|---|---|---|
| K | NiCr – NiAl | −200…+1,200 °C | standard type, oxidation-resistant |
| N | NiCrSi – NiSi | −200…+1,300 °C | more stable than K in long-term use |
| J | Fe – CuNi | −40…+750 °C | economical, reducing atmosphere |
| T | Cu – CuNi | −200…+350 °C | low temperatures, refrigeration |
| E | NiCr – CuNi | −200…+900 °C | highest thermoelectric voltage |
| S | Pt10Rh – Pt | 0…+1,600 °C | noble metal, glass and calibration |
| R | Pt13Rh – Pt | 0…+1,600 °C | noble metal, like S |
| B | Pt30Rh – Pt6Rh | +600…+1,700 °C | highest temperatures |
Colour coding of cables to IEC 60584-3: sheath and positive conductor in the type colour, negative conductor white.
Colour coding to IEC 60584-3
Sheath and positive conductor carry the type colour, the negative conductor is always white. This lets you identify thermocouple and compensating cables without a measuring instrument.
| Type | Sheath and positive conductor | Negative conductor | Colour |
|---|---|---|---|
| K | green | white | #009640 |
| J | black | white | #1A1A1A |
| N | pink | white | #F2A0BD |
| T | brown | white | #7B4B2A |
| E | violet | white | #6F3F9E |
| R, S | orange | white | #EF7D00 |
| B | grey | white | #8C8C8C |
Colours to IEC 60584-3. The marking on the supplied cable remains authoritative.
Tolerances to IEC 60584-1
| Type | Class 1 | Class 2 | Class 3 |
|---|---|---|---|
| T | −40…350: ± 0.5 °C or 0.004·|t| | −40…350: ± 1.0 °C or 0.0075·|t| | −200…40: ± 1.0 °C or 0.015·|t| |
| E | −40…800: ± 1.5 °C or 0.004·|t| | −40…900: ± 2.5 °C or 0.0075·|t| | −200…40: ± 2.5 °C or 0.015·|t| |
| J | −40…750: ± 1.5 °C or 0.004·|t| | −40…750: ± 2.5 °C or 0.0075·|t| | – |
| K, N | −40…1,000: ± 1.5 °C or 0.004·|t| | −40…1,200: ± 2.5 °C or 0.0075·|t| | −200…40: ± 2.5 °C or 0.015·|t| |
| R, S | 0…1,100: ± 1.0 °C; 1,100…1,600: ± [1 + 0.003·(t − 1,100)] | 0…1,600: ± 1.5 °C or 0.0025·|t| | – |
| B | – | 600…1,700: ± 0.0025·|t| | 600…1,700: ± 4.0 °C or 0.005·|t| |
Reference temperature 0 °C. The larger of the two values applies.
Thermoelectric voltage in mV, reference junction 0 °C
| °C | Type K | Type N | Type J | Type S |
|---|---|---|---|---|
| −200 | −5.891 | – | −7.890 | – |
| −100 | −3.554 | −2.407 | −4.633 | – |
| 0 | 0 | 0 | 0 | 0 |
| 100 | 4.096 | 2.774 | 5.269 | 0.646 |
| 200 | 8.138 | 5.913 | 10.779 | 1.441 |
| 300 | 12.209 | 9.341 | 16.327 | 2.323 |
| 400 | 16.397 | 12.974 | 21.848 | 3.259 |
| 500 | 20.644 | 16.748 | 27.393 | 4.233 |
| 600 | 24.905 | 20.613 | 33.102 | 5.239 |
| 700 | 29.129 | 24.527 | 39.132 | 6.275 |
| 800 | 33.275 | 28.455 | – | 7.345 |
| 900 | 37.326 | 32.371 | – | 8.449 |
| 1,000 | 41.276 | 36.256 | – | 9.587 |
| 1,100 | 45.119 | 40.087 | – | 10.757 |
| 1,200 | 48.838 | 43.846 | – | 11.951 |
Thermoelectric voltage over temperature, reference junction 0 °C. Type J rises most steeply but ends at +750 °C; type S gives the smallest voltage and reaches furthest.
Measuring junction insulated or grounded
- Insulated — the thermocouple is galvanically isolated from the sheath. Interference-proof, our standard.
- Grounded — the thermocouple is welded to the sheath bottom. Shorter response time, half-value time from about 0.15 s for small diameters.
Insulated or grounded — the difference lies in the tip and determines interference immunity and response time.
Sheath materials
Inconel 600 / 2.4816 up to 1,150 °C, 1.4571 and 1.4404 up to 800 °C. Special materials such as Nicrofer, Hastelloy, Inconel 601 and tantalum on request. The complete list of materials can be found under Materials.
Which type for your measuring point?
Tell us medium, temperature and required accuracy — we will tell you which type and class make sense there.
The types at a glance
Tolerances
Thermoelectric voltage in mV
Insulated or grounded
Sheath materials
All thermocouples
Thermowell thermocouples
Sheathed thermocouples
Compensating cables
Pt100 or thermocouple?
Question about the design?
Tell us medium, temperature and installation — you will receive a proposal within one working day.